Did you install the condenser upside down and backwards?

July 27, 2021

The vehicle was a 1998 Chevrolet C 1500 truck with a 5.7 engine. The issue was excessive high side pressure. Almost as soon as the compressor clutch engaged, the high side pressure was over 400 PSI, and the high-pressure cut-off was turning the compressor on and off.
Read Article >

Low refrigerant charge and the search for real data part 3

July 6, 2021

To place as much heat load on the system as possible, we turned the heat in the shop up on high and got it as hot as possible before beginning the test. When the temperature peaked at 89°, we began the test. We tried to keep it constant, but all the heat being generated by the engine in the test vehicle caused it to inch upward by 2.5° before the second test was concluded.
Read Article >

What’s the word on R-134a price & supply?

June 24, 2021

The email questions are already coming in, and they go kind of how you’d expect: What’s going on with the price of R-134a? Is there going to be a shortage of R-134a supply?
Read Article >

Low refrigerant charge and the search for real data

June 22, 2021

I had read about how low refrigerant charges could increase compressor operating temperatures and decrease the amount of oil flowing to compressors, but I had never been able to find results from any tests. After discussing this with MACS, we decided to do some testing to get some real data.
Read Article >

Time to make your Rosen Centre Hotel reservation for MACS Training Event

June 10, 2021

Time is running out to make your 2021 MACS Training Event and Trade Show hotel reservation at the Rosen Centre
Read Article >

Electrification and climate control technologies: Are we prepared?

June 3, 2021

A recent survey from CarGurus suggests consumer interest in purchasing an electric vehicle (EV) has doubled in the past three years.
Read Article >

Focus on the condenser!

May 31, 2021

In last week's article, we focused on applying temperature testing to an evaporator in an orifice tube system. In it we illustrated how and why a low liquid level in the evaporator can cause a large temperature differential between the inlet and outlet. We also indicated how and why raising the liquid level will cause the temperature differential to decrease. Now it is time to focus on the condenser.
Read Article >

What is your temperature testing data telling you?

May 18, 2021

If air conditioning systems were transparent where we could see inside them, then diagnostics would be faster and easier. We could look at the systems and see things right away that affect system operation, like restrictions and liquid levels in evaporators and condensers.
Read Article >

Temperature Matters

May 11, 2021

In addition to having good contact with connectors and getting accurate readings, there are some other important things to remember when doing temperature testing.
Read Article >

Pass the temperature probe

May 4, 2021

The first step is to run the A/C system for a few minutes to let it stabilize. Then both probes should be connected side by side at both points that will be temperature tested in the system. For example, if you were testing the temperature drop across the condenser, this would need to be done on both the discharge line and the liquid line.
Read Article >